Poor Attic Ventilation Can
Ruin Your Insulation,
Destroy Your Shingles, And Raise Your Energy Bills!
Why Take Risks?
It is estimated that 9 out of 10 homes in North
America do not have proper attic ventilation. Why? Because most people
are unaware that attic ventilation can impact the longevity of their entire
home!
For example, in the summer,
an improperly ventilated attic can cause heat to build in excess of 160°F.
This superheated air eventually penetrates the ceiling insulation into
the living area below.
Types of damage that can
result
include:
- Premature aging of your roofing system (fried shingles)
- Warping, cracking, or breaking down of wood framing
- Damage to siding, exterior or interior paint, and wallpaper
- Higher energy costs
A properly ventilated attic can help reduce the load on your air conditioner
by moving the superheated air out of your attic before it builds up and
causes damage.
In the winter, various household appliances,
bathtubs, showers, and cooking vapors can contribute to excess moisture
build-up. Improperly ventilated attics will allow this moisture to collect
and cling to the underside of the roof. There, it will condense and fall,
soaking the attic insulation and reducing its efficiency
Additional structural damage
can include:
- Roof deck warping and rotting of the wood frame
- Mildew growth
- Buckling of shingles and felt
Finally,
attics should be properly ventilated to help prevent ice dams in cold
northern climates. During the winter, ice and snow on a roof will melt
and run down the deck to the cooler eaves. This run-off can re-freeze,
creating an ice dam that will trap moisture on the roof. The moisture
can eventually back up under the shingles and enter your home causing
hundreds or thousands of dollars of damage to your ceilings and walls.
Adequate attic ventilation will reduce the amount of initial melting that
occurs on your roof, thereby reducing the chance that ice dams will form.
Proper Attic Ventilation
Proper attic ventilation systems allow a continuous
flow of outside air through the attic (see illustration at left), protecting the efficiency of the insulation and helping to lower
temperatures in the living space.
It consists of a balance between air intake
(at your eaves or soffits) and air exhaust
(at or near your roof ridge).
The FHA (Federal Housing Administration) recommends a minimum of at least 1 square foot of attic ventilation (both intake and exhaust)
for every 300 square feet of attic space. For example, if your attic is
900 square feet, you need a total of 3 square feet of ventilation. This
amount is generally divided equally between intake and exhaust ventilation
(i.e., 11/2 feet of each), to insure proper air flow through the attic.
To calculate the amount of ventilation you need for your home, follow
the example shown on the next page.
|
 |

Calculating Your
Ventilation Requirements
Example: Calculating the number of lineal feet
of Cobra® Exhaust Vent needed for a 30x 40 attic: |
| Step 1 |
Calculate attic square footage
How: Multiply length of attic (in feet) times width of attic (in feet)
30 x 40 = 1,200 square
feet |
Intake ventilation MUST be at least equal to exhaust
ventilation. To determine the number of intake vents needed, select your
vent on page 12, and install enough vents so that their combined NFA is
at least 288 square inches.
Remember:
Always have a balanced ventilation
system. In no case should the amount of exhaust ventilation exceed the
amount of intake
ventilation. |
| Step 2 |
Calculate NFA (Net Free Area) needed for
this attic by using the 1 in 300 rule
How: Divide attic square footage by 300
1,200 sq. ft. ÷ 300 = 4 square
feet of NFA needed |
| Step 3 |
Convert square feet of NFA to square inches
How: Multiply square feet of NFA by 144
4 sq. ft. x 144 = 576 square inches
of NFA needed |
| Step 4 |
Split the amount of NFA needed equally between
the intake and the exhaust
How: Divide square inches of NFA needed by 2
576 sq. in. ÷ 2 = 288 square
inches of NFA needed equally for exhaust & intake |
| Step 5 |
Calculate # of lineal feet of Cobra®
Exhaust Vent needed
How: Divide the square inches of NFA needed at the ridge by the NFA of
the Cobra® Exhaust Vent
(Cobra® Exhaust Vent has 16.9 sq. inches of NFA per lineal foot)
288 sq. in. ÷ 16.9 = 17 lineal
feet
This attic requires seventeen (17) lineal feet
of Cobra® Exhaust Vent to meet FHA minimum requirements. |
| |
|
|
|